EnwaMatic®
Continuous Side-Stream
Filtration &
Self Regulating Water
Treatment.
'Send us your enquiry'
Designed to enhance the performance, protection and profitability of HVAC systems.
Function
- Regulates pH, Alkalinity & Hardness
- Inhibits Corrosion
- Scale Control
- Side Stream Filtration < 5 microns
- Environmental Control of Bacterial Growth
- Air Separation
Benefits
- Reduced Energy Consumption
- Prolonged System Lifespan
- Reduced Service & Maintenance Costs
- Cost Effective Alternative to Chemical Dosing
- Non Scouring Solution for Refurbishment Projects
- Environmentally Sound Technology
- Reduced Health & Safety Risk
The EnwaMatic® connects permanently within a closed loop HVAC system treating a proportion of the main flow, such that the entire systems volume passes through the unit in less than 24 hours.
Side-stream filters provide effective long term water conditioning without the energy losses associated with in-line devices. As the proportion of flow diverted through the unit is less than 1%, the impact on the energy efficiency of the system is negligible.
Once installed the unit begins to clean the system water and establish it's unique chemistry. Connection to mains or cold water services and a drainage point allows a quick and simple backwash procedure to purge trapped solids from the filter bed.
Units are specified on total HVAC system volume.
"Combination of both continuous filtration and water treatment, with low running costs and a structured maintenance regime, provide an excellent water conditioning package".
William Rowe, Consultant Engineer / Director, Integrated Energy Utilities Ltd.
Return to top
|
|
|
|
|
|
|
|
|
|
|
|
Scale and corrosion control using a combined calcite / dolomite filter
EnwaMatic® Side-Stream Filtration and Water Treatment Units utilise a unique, non-hazardous reaction media of calcite / dolomite composition to regulate pH, alkalinity and hardness. The result is a dynamic carbonate based equilibrium that is self regulating and can react to changes in the quality and quantity of incoming water. The corrosive properties of soft water are neutralised, whilst excess calcium carbonate present in hard water is safely precipitated out within the media bed. (Ref 1, 2, 3) |
|
Effective control of corrosion and scale
Maximum efficiency at heat transfer surfaces
Reduced loss of energy through disproportionate heating or short circuiting
Maintains correct flow rates, ensuring reliable, efficient transport of energy
Prevents excessive wear or seizing of movable components
Prolongs the safe operating lifespan of HVAC plant |
|
|
|
Filtration in HVAC systems
By-products of corrosion and scale formation, installation debris and general fouling can create a high suspended solids loading in closed systems. This can impact on the energy transport characteristics of the water and disrupt fluid flow rate and distribution. Particles can become lodged in movable components such as automated valves and will block strainers, accelerate erosion and lead to sludge deposits in low flow areas. EnwaMatic® side stream filtration is to less than 5 microns and independent tests have shown suspended solids in closed systems reduce to levels comparable with potable water. (Ref 1) |
|
Restricting development of microbial organisms
The EnwaMatic® Side Stream Filtration & Water Treatment Units create a harsh environment for bacterial development. pH is maintained above 9, severely restricting cell wall replication whilst conditioning removes the nutrients, flow restrictions and protective layers which promote growth of bacterial colonies. Maintaining a vey clean system allows more effective biocidal dosing and the EnwaMatic® is complimentary to more aggressive strategies aimed at problem species such as Pseudomonas. |
|
|
Return to top
Energy and the environment
The EnwaMatic® Side-Stream Filtration & Water Treatment unit is complimentary to the objectives of modern environmental management systems and regulations.
Ensuring optimal conditions for energy transfer at heat exchange surfaces EnwaMatic®:
Maintains correct water flow rate and distribution throughout the building
Boilers and chillers are able to operate within their designed parameters
Pumps are required to do less work, draw less current and wear less quickly
Ensures correct function of manual and automated valves, enabling efficient building managment
Prolongs the safe, effective life span of system components
Environmentally safe reaction media reduces the risks associated with site storage, handling and disposalAberdeen City Council realise savings of upto 13% with an average 8% reduction in energy consumption. All data compiled by ACC Energy Department.
Moelv, Ringsaker Municipality Norway.
Documented savings of 6.5% in energy costs for heating during a pilot project, 1999/2000. Data compared against extensive archive.
|
|
|
IMAG Optical Storage Ltd, Limerick, Ireleand.
Effective performance of air handling units restored. 50% reduction in mean pumping energy requirement. Increased alignmnent with implementation of ISO 14001. |
|
Crystal Harmony Cruise Liner
Estimated 2000 - 3000 kg particulate sludge removed post installation of EnwaMatic® 33% improvement in compressor efficiency under comparable load conditions. |
|
|
|
|
|
|
|
|
ENWA UK & Eire, 57 High Street, Ibstock, Leicestershire, LE67 6LH.
Tel: 01530 260647, e-mail: info@enwa.co.uk, Fax: 01530 264 184
|
|
|
|
|
|